Product details of the arc furnace transformer design
Product Information
Ville Transformer arc furnace transformer design is precisely manufactured using premium materials and leading-edge techniques. a team of skilled quality controllers handles the quality checks that are conducted to examine and ensure the flawlessness of the offered products. In the fierce market competition, INGBO VILLE ENTERPRISE CO.,LTD. has won the recognition of domestic and international markets with arc furnace transformer design.
BASIC INFO.
Model NO. | HSSPZ-144000/33 | No Load Losses | 52kw |
Cooling Method | Oil-immersed Type Transformer | Load Losses at 75 | 280 Kw ( 60mva 950V ) (Including LV Lead Losses |
Winding Type | Multi-winding Transformer | Cooling System | Ofwf, Double Tube, 2 Coolers in Service. |
Usage | Electric Arc Furnace Transformer | On-Load Tap Changer | Mr |
Frequency Characteristics | Power Frequency | Testing | Routine Test According to IEC Standard |
Shape of Core | Ring | Transport Package | Nuke Packing; Wooden Cases |
Brand | Ville | Specification | IEC |
Arc | Furnace Transformer | Trademark | Ville |
Steel | Furnace | Origin | Ningbo China |
Type | Calcium Carbide Furnace Transformer | HS Code | 8514901000 |
Test Certification | Kema | Production Capacity | 10/Years |
Reference Standard | IEC 60076 |
THE MEANING OF MODEL
H--Steelmaking arc furnace,HJ--ladle furnace,HZ--electro-slag furnace,HC--calcium carbide furnace,HK--mineralhot furnace,HG--line frequency induction furnace;
Number of phase:D--single phase,S--three phase;
Types of cooling device :ONAN,wind cooling F,water cooling S.
The methods of oil circulation:natural circulation,forced oilcirculation P.
Tap changer:off-circuit tap changer,OLTC Z.
Enclosed attached device:changing leakage flux,enclosed reactor K.
Rated capacity:KVA. max 140MVA
Voltage class:KV. 35KV
TECHNICAL PARAMETERS
General data
|
|
Operating Voltage |
33KV±3% |
Frequency |
50Hz±1% |
Rated capacity |
144 MVA |
Over load power |
144MVA plus 20%,30 min. |
Rated primary current |
1049.7 A |
Insulation Level (AC/LI) |
85/200 kV |
Vector group |
D/d0 with booster regulation transformer inside. |
Secondary connection |
Delta OPEN |
System short circuit capacity at 33kV side. |
1100 MVA |
Secondary outlet |
Terminals with Bus bars come out from top cover. 8 Buss bars by epoxy resin arranged along with each phase with matching cite transformer sizes. |
Max. Secondary current |
Approximate 42120 A |
Secondary voltage range |
950-500 V. |
a) Constant power |
950V-822.4 V at 60 MVA |
b) Constant current |
About 42062 A within 824V-500V |
c) Short-circuit voltage |
8 % (at 950V,60MVA) |
Type of tap changer |
On load tap-changer: |
a) Manufacturer |
MR, |
b) Number of tapes |
17 voltage steps with 18position See attached data sheet of 60MVA EAF transformer. |
c) Oil filter equipment for OLTC |
yes |
Cooling |
OFWF |
Company Advantage
• Ville Transformer pays attention to talents management and cooperation. We have a high-quality and highly-educated elite team.
• Ville Transformer was built in Having developed the business for years, we are now a leading enterprise in the industry. We are equipped with advanced production equipment and strong technical capability.
• Ville Transformer advocates to focus on customer's feelings and emphasizes humanized service. We also wholeheartedly serve for every customer with the work spirit of 'strict, professional and pragmatic' and the attitude of 'passionate, honest, and kind'.
• Ville Transformer not only sells transformer in the domestic market, but also exports them to many overseas countries and regions.
Ville Transformer is really glad to provide you with business consulting. Feel free to contact us.